Expansion valves play a crucial role in regulating refrigerant flow in central air conditioning and refrigeration systems. Their proper operation ensures that the cooling capacity matches the required evaporation temperature of the system. Issues with expansion valve flow, whether excessive or insufficient, can significantly impact the HVAC system’s overall performance. Let’s discuss how to diagnose and address these issues effectively.
1. Expansion Valve Flow Characteristics
The flow rate of an expansion valve should be adjusted to match the required evaporative cooling load at a given superheat level. During the initial installation and commissioning of refrigeration or central air conditioning equipment, the valve is typically set to maintain the desired evaporation temperature range. Under normal operating conditions, the valve adjusts automatically based on the system’s thermal load.

However, if changes in the system’s conditions occur—such as reduced compressor displacement, elevated condensing temperatures, or variations in refrigerant charge due to maintenance—the expansion valve may fall outside its automatic adjustment range. In these cases, manual recalibration of the valve is necessary.
2. Symptoms of Incorrect Expansion Valve Flow
• High Evaporator Pressure with Inability to Lower It: This indicates that the evaporation temperature is too high, leading to insufficient cooling in the chilled space. To correct this, the expansion valve must be readjusted. However, setting it too low can result in inadequate refrigerant flow, further hampering cooling performance.
• Frost Pattern Analysis: Monitoring frost formation on the suction line provides insights into flow rate issues.
• Excessive Flow: If frost extends to the suction shut-off valve and the evaporator pressure is too high, the expansion valve’s flow is likely excessive.
• Insufficient Flow: If frost does not reach the suction line, it suggests the expansion valve flow is too low.

Static performance curve of expansion valve
3. Conditions for Accurate Diagnosis
It is important to assess evaporator pressure .Not only after the system has been running continuously for an extended period (at least one hour). During this time, the heat load in the chilled space should remain relatively stable. This ensures that the pressure readings accurately reflect the system’s steady-state conditions.
4. Step-by-Step Guide to Adjusting the Expansion Valve
• Gradual Adjustment: Turn the valve stem in increments of 1/4 to 1/2 turn, then run the system for about 20 minutes before observing changes in suction pressure. This waiting period allows time for heat exchange in the chilled space and for the thermal bulb of the expansion valve to respond to changes in superheat.
• Fine-Tuning: If there is no significant change in suction pressure after an initial adjustment, continue making incremental adjustments. Avoid drastic changes, as overly reducing the valve opening can sharply decrease flow rate. slowing down the cooling process and potentially preventing the system from reaching the target temperature.
5. Common Pitfalls and Best Practices
• Avoid Overcorrection: Over-adjusting the expansion valve can lead to a sharp drop in refrigerant flow, which may cause the evaporation pressure to stabilize at a higher level than desired. This can slow down the cooling rate, making it challenging to achieve the set temperature.
• Patience is Key: After each adjustment, wait approximately 20 minutes. This delay accounts for the time required for the chilled space to reach thermal equilibrium and for the thermal bulb’s superheat adjustments to take effect.

By understanding and correctly diagnosing expansion valve flow problems, HVAC technicians can ensure the optimal performance of refrigeration and air conditioning systems. Proper calibration not only improves energy efficiency but also extends the lifespan of the equipment.